View other products

INSX100N MCCB

Circuit breaker Compact INSX100N 3P 80A 3d

If you have any questions, please contact us!
Main
Device short name Compact INSX100N
Circuit breaker application Distribution
Poles description 3P
Protected poles description 3t
Network type AC
Network frequency 50/60 Hz
[In] rated current 100 A ( 40 °C )
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV
[Ue] rated operational voltage 690 V AC 50/60 Hz
Circuit breaker rating code N
Breaking capacity Icu 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
Icu 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Icu 90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Icu 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
Icu 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Icu 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
90 kA at 240 V AC 50/60 Hz conforming to NEMA AB1
50 kA at 480 V AC 50/60 Hz conforming to NEMA AB1
20 kA at 600 V AC 50/60 Hz conforming to NEMA AB1
85 kA at 240 V AC 50/60 Hz conforming to UL 508
50 kA at 480 V AC 50/60 Hz conforming to UL 508
20 kA at 600 V AC 50/60 Hz conforming to UL 508
[Ics] rated service breaking capacity Ics 10 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Ics 35 kA 525 V AC 50/60 Hz conforming to IEC 60947-2
Ics 36 kA 500 V AC 50/60 Hz conforming to IEC 60947-2
Ics 50 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2
Ics 50 kA 440 V AC 50/60 Hz conforming to IEC 60947-2
Ics 90 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Suitability for isolation Yes conforming to IEC 60947-2
Yes conforming to EN 60947-2
Utilisation category Category A
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Trip unit rating 80 A ( 40 °C )
Protection type Overload protection (thermal)
Short-circuit protection (magnetic)
Pollution degree 3 conforming to IEC 60947-1
Complementary
Control type Toggle
Mounting mode Fixed
Mounting support Backplate
Upside connection Front
Downside connection Front
Mechanical durability 50000 cycles
Electrical durability 50000 cycles 440 V In/2 conforming to IEC 60947-2
30000 cycles 440 V In conforming to IEC 60947-2
20000 cycles 690 V In/2 conforming to IEC 60947-2
10000 cycles 690 V In conforming to IEC 60947-2
Connection pitch 35 mm
Local signalling Positive contact indication
Long time pick-up adjstment type Ir Adjustable
Long time pick-up adjustment range 0.7...1 x In
Long time delay adjustment type Fixed
[tr] long-time delay adjustment 15 s 6 x Ir
120...400 s 1.5 x In
Short-time pick-up adjustment type Isd Fixed
[Isd] short-time pick-up adjustment range 640 A
Short-time delay adjustment type Fixed
Height 161 mm
Width 105 mm
Depth 86 mm
Environment
Electrical shock protection class Class II
Standards EN 60947-2
IEC 60947-2
NEMA AB1
UL 508
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to EN 50102
Ambient air temperature for operation -35...70 °C
Ambient air temperature for storage -55...85 °C

Email

accontactor@163.com
Email

Skype

snowyandsky
Skype

Skype

lily.hong9
Skype

Phone

0086-577-62125022
Phone