Device short name |
Compact INSX100N
|
Circuit breaker application |
Distribution
|
Poles description |
3P
|
Protected poles description |
3t
|
Network type |
AC
|
Network frequency |
50/60 Hz
|
[In] rated current |
100 A ( 40 °C )
|
[Ui] rated insulation voltage |
800 V AC 50/60 Hz
|
[Uimp] rated impulse withstand voltage |
8 kV
|
[Ue] rated operational voltage |
690 V AC 50/60 Hz
|
Circuit breaker rating code |
N
|
Breaking capacity |
Icu 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
Icu 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 Icu 90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 Icu 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 Icu 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 Icu 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 90 kA at 240 V AC 50/60 Hz conforming to NEMA AB1 50 kA at 480 V AC 50/60 Hz conforming to NEMA AB1 20 kA at 600 V AC 50/60 Hz conforming to NEMA AB1 85 kA at 240 V AC 50/60 Hz conforming to UL 508 50 kA at 480 V AC 50/60 Hz conforming to UL 508 20 kA at 600 V AC 50/60 Hz conforming to UL 508 |
[Ics] rated service breaking capacity |
Ics 10 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Ics 35 kA 525 V AC 50/60 Hz conforming to IEC 60947-2 Ics 36 kA 500 V AC 50/60 Hz conforming to IEC 60947-2 Ics 50 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2 Ics 50 kA 440 V AC 50/60 Hz conforming to IEC 60947-2 Ics 90 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
Suitability for isolation |
Yes conforming to IEC 60947-2
Yes conforming to EN 60947-2 |
Utilisation category |
Category A
|
Trip unit name |
TM-D
|
Trip unit technology |
Thermal-magnetic
|
Trip unit rating |
100 A ( 40 °C )
|
Protection type |
Overload protection (thermal)
Short-circuit protection (magnetic) |
Pollution degree |
3 conforming to IEC 60947-1
|
Control type |
Toggle
|
Mounting mode |
Fixed
|
Mounting support |
Backplate
|
Upside connection |
Front
|
Downside connection |
Front
|
Mechanical durability |
50000 cycles
|
Electrical durability |
50000 cycles 440 V In/2 conforming to IEC 60947-2
30000 cycles 440 V In conforming to IEC 60947-2 20000 cycles 690 V In/2 conforming to IEC 60947-2 10000 cycles 690 V In conforming to IEC 60947-2 |
Connection pitch |
35 mm
|
Local signalling |
Positive contact indication
|
Long time pick-up adjstment type Ir |
Adjustable
|
Long time pick-up adjustment range |
0.7...1 x In
|
Long time delay adjustment type |
Fixed
|
[tr] long-time delay adjustment |
15 s 6 x Ir
120...400 s 1.5 x In |
Short-time pick-up adjustment type Isd |
Fixed
|
[Isd] short-time pick-up adjustment range |
800 A
|
Short-time delay adjustment type |
Fixed
|
Height |
161 mm
|
Width |
105 mm
|
Depth |
86 mm
|
Electrical shock protection class |
Class II
|
Standards |
EN 60947-2
IEC 60947-2 NEMA AB1 UL 508 |
IP degree of protection |
IP40 conforming to IEC 60529
|
IK degree of protection |
IK07 conforming to EN 50102
|
Ambient air temperature for operation |
-35...70 °C
|
Ambient air temperature for storage |
-55...85 °C
|