Specifications:
AC 50Hz/60Hz
rated voltage 230V
used as electron shock protection
It can protect circuit form overload and short circuit

Application
TDPNa+vigi is used in the single phase circuit of AC 50Hz/60Hz, rated voltage 230V, used as electron shock protection. It can protect circuit form overload and short circuit. This product has advantages of small volume, high breaking capacity, live and zero wire are cut off at the same time, also protecting person from electric shock when the live wire connected opposite. It conforms with the standards of IEC61009.

Main Technical Parameter
Type
TDPNa+vigi
Pole
1P+N
Rated current (A)
6,10,16,20,25,32
Rated voltage(V)
230
Rated residual action current In(A)
0.03
Rated residual non-action current Ino(A)
0.015
Rated residual making/breaking capacity Im(A)
500
Type of instantaneous release
C
Rated making/breaking capacity Im(A)
4500

Applicable conducting wire
Rated current(A)
Nominal cross section of wire mm2
In ≤ 6
1
6< In ≤ 13
1.5
13 < In ≤ 20
2.5
20 < In ≤ 25
4
25 < In ≤ 32
6

Residual current breaking time
In (A)
In (A)
Breaking time(s) when equals to rating following
In
2In
5In
5,10,20,50,100,200,500a(A)
Itb
6-32
0.03
0.1
0.06
0.04
0.04
0.04

The over-current protection property
Ambient Temperature
Initial Status
Test Current
Expected Result
Expected Result
Note
 
Cold position
1.13In
t ≥ 1h
Non-release
-
30±2oC
Carried out immediately after previous test
1.45In
t<1h
Release
-
 
Cold position
2.55In
1s < t < 60s
Release
Current smoothly rises to specified value within 5s
-5~+40oC
Cold position
5In
t ≥ 0.1s
Non-release
Type C
Cold position
10In
t < 0.1s
Release
Type C

 
 