View other products

TC65 MCB

Tc65+vigi 2P RCCB

If you have any questions, please contact us!

Specifications:
AC 50Hz/60Hz
rated voltage 230V
used as electron shock protection
It can protect circuit form overload and short circuit


Application
TDPNa+vigi is used in the single phase circuit of AC 50Hz/60Hz, rated voltage 230V, used as electron shock protection. It can protect circuit form overload and short circuit. This product has advantages of small volume, high breaking capacity, live and zero wire are cut off at the same time, also protecting person from electric shock when the live wire connected opposite. It conforms with the standards of IEC61009.

Main Technical Parameter

Type

TDPNa+vigi

Pole

1P+N

Rated current (A)

6,10,16,20,25,32

Rated voltage(V)

230

Rated residual action current In(A)

0.03

Rated residual non-action current Ino(A)

0.015

Rated residual making/breaking capacity Im(A)

500

Type of instantaneous release

C

Rated making/breaking capacity Im(A)

4500


Applicable conducting wire


Rated current(A)

Nominal cross section of wire mm2

In ≤ 6

1

6< In ≤ 13

1.5

13 < In ≤ 20

2.5

20 < In ≤ 25

4

25 < In ≤ 32

6


Residual current breaking time


In (A)

In (A)

Breaking time(s) when equals to rating following

In

2In

5In

5,10,20,50,100,200,500a(A)

Itb

6-32

0.03

0.1

0.06

0.04

0.04

0.04


The over-current protection property


Ambient Temperature

Initial Status

Test Current

Expected Result

Expected Result

Note

 

Cold position

1.13In

t ≥ 1h

Non-release

-

30±2oC

Carried out immediately after previous test

1.45In

t<1h

Release

-

 

Cold position

2.55In

1s < t < 60s

Release

Current smoothly rises to specified value within 5s

-5~+40oC

Cold position

5In

t ≥ 0.1s

Non-release

Type C

Cold position

10In

t < 0.1s

Release

Type C