| Device short name |
Compact INSX100F
|
| Circuit breaker application |
Distribution
|
| Poles description |
3P
|
| Protected poles description |
3t
|
| Network type |
AC
|
| Network frequency |
50/60 Hz
|
| [In] rated current |
100 A ( 40 °C )
|
| [Ui] rated insulation voltage |
800 V AC 50/60 Hz
|
| [Uimp] rated impulse withstand voltage |
8 kV
|
| [Ue] rated operational voltage |
690 V AC 50/60 Hz
|
| Circuit breaker rating code |
F
|
| Breaking capacity |
Icu 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
Icu 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 Icu 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 Icu 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 Icu 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 Icu 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 85 kA at 240 V AC 50/60 Hz conforming to NEMA AB1 35 kA at 480 V AC 50/60 Hz conforming to NEMA AB1 8 kA at 600 V AC 50/60 Hz conforming to NEMA AB1 85 kA at 240 V AC 50/60 Hz conforming to UL 508 25 kA at 480 V AC 50/60 Hz conforming to UL 508 10 kA at 600 V AC 50/60 Hz conforming to UL 508 |
| [Ics] rated service breaking capacity |
Ics 4 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Ics 11 kA 525 V AC 50/60 Hz conforming to IEC 60947-2 Ics 12.5 kA 500 V AC 50/60 Hz conforming to IEC 60947-2 Ics 35 kA 440 V AC 50/60 Hz conforming to IEC 60947-2 Ics 36 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2 Ics 85 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| Suitability for isolation |
Yes conforming to IEC 60947-2
Yes conforming to EN 60947-2 |
| Utilisation category |
Category A
|
| Trip unit name |
TM-D
|
| Trip unit technology |
Thermal-magnetic
|
| Trip unit rating |
25 A ( 40 °C )
|
| Protection type |
Overload protection (thermal)
Short-circuit protection (magnetic) |
| Pollution degree |
3 conforming to IEC 60947-1
|
| Control type |
Toggle
|
| Mounting mode |
Fixed
|
| Mounting support |
Backplate
|
| Upside connection |
Front
|
| Downside connection |
Front
|
| Mechanical durability |
50000 cycles
|
| Electrical durability |
50000 cycles 440 V In/2 conforming to IEC 60947-2
30000 cycles 440 V In conforming to IEC 60947-2 20000 cycles 690 V In/2 conforming to IEC 60947-2 10000 cycles 690 V In conforming to IEC 60947-2 |
| Connection pitch |
35 mm
|
| Local signalling |
Positive contact indication
|
| Long time pick-up adjstment type Ir |
Adjustable
|
| Long time pick-up adjustment range |
0.7...1 x In
|
| Long time delay adjustment type |
Fixed
|
| [tr] long-time delay adjustment |
15 s 6 x Ir
120...400 s 1.5 x In |
| Short-time pick-up adjustment type Isd |
Fixed
|
| [Isd] short-time pick-up adjustment range |
300 A
|
| Short-time delay adjustment type |
Fixed
|
| Height |
161 mm
|
| Width |
105 mm
|
| Depth |
86 mm
|
| Electrical shock protection class |
Class II
|
| Standards |
EN 60947-2
IEC 60947-2 NEMA AB1 UL 508 |
| IP degree of protection |
IP40 conforming to IEC 60529
|
| IK degree of protection |
IK07 conforming to EN 50102
|
| Ambient air temperature for operation |
-35...70 °C
|
| Ambient air temperature for storage |
-55...85 °C
|